Minimum Distributed Live Loads |
||||||||
use or occupancy |
Uni -form kPa |
Con -centra ted kN |
use or occupancy |
Uniform kPa |
Con -centra ted kN |
use or occupancy |
Uniform kPa |
Concen -tra ted kN |
Access floor systems office use |
2,4 |
8,9 |
Kitchen general area |
12 |
|
Post Office general area |
4,8 |
|
Access floor systems computer use |
4,8 |
8,9 |
Kitchen provision storage |
9,6 |
|
Post Offices work room |
6,0 |
|
Safety storage |
23,9 |
- |
Kitchen preparation room meat |
12 |
|
Power plants |
9,6 |
|
Assembly areas & theaters fixed seats |
2,9 |
|
Kitchen preparation room vegetable |
4,8 |
|
Pump houses |
4,8 |
|
Assembly areas & theaters |
4,8 |
|
Garage(pas -senger vehicle |
1,9 |
|
Recreation room |
4,8 |
|
Assembly .areas & theaters movable seats |
4,8 |
|
Generator room |
9,6 |
|
Residential uninhabi-table attics with storage |
1,0 |
|
Stages and platforms |
6,0 |
|
Guard house |
3,6 |
|
Residential habitable attics and sleeping areas |
1,4 |
|
Follow spot, projection & control rooms |
2,4 |
|
Gymnasium, main floor |
4,8 |
|
Residential balconies and deck |
1,9 |
|
Catwalks |
1,9 |
|
Hospital operating rooms, laboratories |
2,9 |
|
Residential public rooms and corridors |
4,8 |
|
Balconies (exterior) |
4,8 |
|
Hospital private rooms |
1,9 |
|
Schools classrooms |
1,9 |
4,45 |
Balconies on one - two families(<9m2) |
2,9 |
|
Hospital wards |
1,9 |
|
Schools corridors |
4,8 |
4,45 |
Battery charging rooms |
9,6 |
|
Hospital corridors |
3,8 |
|
Sideways, vehicular driveways, for trucks |
12 |
|
Boiler houses |
9,6 |
|
Incinerators, charging room |
7,2 |
|
Stadiums and arena bleachers |
4,8 |
|
Bowling alleys |
3,6 |
|
Laboratories normal scientific equipment |
6,0 |
|
Stairs and exits publics |
4,8 |
|
cleaning gear/trash room, compactor |
3,6 |
|
Latrines, toilets |
3,6 |
|
Stores retail first floor |
4,8 |
4,45 |
Cold storage (food) first floor |
19,2 |
|
Libraries reading rooms |
2,9 |
|
Stores retail upper floor |
3,6 |
4,45 |
Cold storage (food) upper floors |
14,4 |
|
Libraries stack rooms |
7,2 |
|
Stores retail wholesale |
6 |
4,45 |
Cornices |
2,9 |
|
Manufacturing light |
6 |
|
Storage warehouses light |
6 - 9,6 |
|
Corridors (except otherwise) |
4,8 |
|
Manufacture heavy |
12 |
|
Storage warehouses heavy |
12 - 23 |
|
Court rooms |
3,8 |
|
Manufacturing shops & industrial light |
6 - 9,6 |
|
Storage warehouses pipe & metals |
48 |
|
Dance halls & ballrooms |
4,8 |
|
Manufacturing shops & industrial heavy |
12 - 14,4 |
|
Stadiums and arena fixed seats |
2,9 |
|
Dining rooms and restaurants |
4,8 |
|
Mechanical equipment |
4,8 |
|
Tailor shop |
3,6 |
|
Elevator machine room |
|
1,33 |
Mechanical room |
6 |
|
Telephone exchange room & central IT server |
7,2 |
|
Electrome- chanical room |
7,2 |
0,89 |
Morgue |
4,8 |
|
Walkways &elevated platforms |
2,9 |
|
Fire escape general |
4,8 |
|
Offices lobbies buildings |
4,8 |
8,9 |
Yards and terraces, pedestrian |
2,9 |
|
Fire escape single family |
1,9 |
|
Penal institution cell blocks |
1,9 |
|
Yards finish light floor plate construct. |
|
|
Galleys dish washing -rooms |
14,4 |
|
Penal institution corridors |
4,8 |
|
|
|
|